Architectural freedom in designing fire-resistant façade elements

Since 1 November 2019, fire-resistant external doors and opening windows have had to bear CE marking based on NEN-EN 16034 in combination with NEN-EN 14351-1.
Fire-resistant solutions are developed by the façade industry, including system suppliers and/or façade contractors, and tested at one of the accredited testing institutes in the Netherlands or neighbouring European countries. Fire-resistant external doors and windows may only bear CE marking if a Notified Body has established that the façade contractor meets the requirements of NEN-EN 16034 and has confirmed this with a Certificate of constancy of performance. The façade contractor manufactures and installs the façade elements and provides the client with a declaration of performance (DoP) for the installed elements.
Architectural freedom
Previously, the knowledge and experience of experts allowed flexibility in the design of bespoke fire-resistant solutions. This has no longer been permitted since 1 November 2019. For non-standard designs, only Direct Applications (NEN EN 1634 1) and/or Extended Applications (NEN EN 15269) may be used. This affects the range of fire-resistant external doors and opening windows available. CE marking for fire-resistant external doors and opening windows therefore has a direct impact on architects’ design freedom. When preparing an initial building design, architects need to check whether the specified fire-resistant external doors and opening windows, including their structural connections, are available with the required classifications. If not, fire-resistant external doors and opening windows and their structural connections can be engineered (developed) and tested in the early stages in collaboration with a façade contractor, or, as a last resort, the design will need to be amended.

The right elements in the right locations
The fire-resistance requirements for a building are set out in the Building Decree. The completed building must comply with the Building Decree. NEN 6068/NEN 6069 can be used to determine which performance requirements apply in which parts of the building.
Fire-resistant external doors and opening windows may only be installed in a building under construction if the performance stated in the declaration of performance and on the CE label meets the requirements for that building. Under the Construction Products Regulation, fire-resistant external doors and opening windows without CE marking may not be offered or placed on the market. If their performance meets the requirements for the building, the construction phase must include checks to ensure that the structural connections being installed also match those that were tested.
The façade sector, together with NEN and commissioned by the Ministry of the Interior and Kingdom Relations, has drawn up a Dutch Practice Guideline (NPR 6112). It sets out the legally applicable fire-resistance requirements and assessment criteria for façade frames with opening parts (windows and doors) in common practical situations. The NPR also explains how these requirements and criteria are recorded in the associated CE marking, ensuring that the CE marking reflects the applicable statutory requirements. The NPR was published in early 2021.
Summary
• From the initial design stage, check whether the specified fire-resistant external doors and opening windows, and their structural connections, are available with the required classifications.
• If the fire-resistant external doors and opening windows, and the structural connections to be used, are not available for the initial design, it is advisable to:
• amend the design, which will save considerable time and cost;
• contact a certified façade contractor at a very early stage. The façade elements and structural connections specified in the design will then need to be developed further and tested.
• Only fire-resistant external doors and opening windows bearing CE marking (DoP) may be offered and supplied. A certified façade contractor is responsible for ensuring this.
• These external doors and opening windows may only be used if the performance stated on the CE label and in the declaration of performance meets the requirements for the building to be constructed;
• When installing fire-resistant external doors and opening windows, checks must be made to ensure that the structural connections being installed match those set out in the report prepared by a Notified Body.