Fire safety of façades

Stay cool, build safely
On 12 March, the VMRG held the online expert session ‘Stay cool, build safely’. The session provided insight into the theory and practice of façade fire safety. Henk Zoontjens, director of the VMRG, discussed the topic with Emiel van Rossum, director and lecturer at Brandpreventie Academy, and Joep Römgens, Head of Service, Product and Marketing at Schüco Benelux.
Fire safety is an important issue in façade construction. The Grenfell Tower fire in England and the fire in a tower block in Valencia are just two examples. When it comes to fire safety, many terms are used interchangeably, including fire spread between buildings, fire penetration and reaction-to-fire classes. This session helped clarify the subject. We look back at some of the questions that were discussed.
Where do the regulations on building fire safety come from?
Emiel van Rossum: The Bbl (Building Environment Decree, formerly the Building Decree) sets out the fire safety regulations. For façades, these are mainly NEN 6068, which covers resistance to fire penetration and fire spread between buildings (WBDBO), and NEN-EN 13501-1, which sets out the reaction-to-fire classes, in other words the combustibility of materials. NEN 6068 refers to NEN 6069 for the fire resistance of materials.
On NEN 6068, could you explain exactly what fire penetration and fire spread between buildings mean?
Emiel van Rossum: Fire spread between buildings occurs through the outside air. It can spread to another building
or, via the outside air, to an upper floor of the same building, for example. Fire penetration is the spread of fire through a building element within the building. Ultimately, all possible routes must be considered, including ventilation grilles.
If a WBDBO of 60 min is required, can this be divided between two elements, each providing 30 minutes, in a fire spread scenario?
Emiel van Rossum: For vertical fire spread, you need to consult both NEN 6068 and Table 2 of NEN 6069. This is quite a complex subject and should be left to the person carrying out the fire spread calculations. But two elements, each providing 30 minutes of fire resistance from both sides, should always be sufficient. In practice, the required performance will therefore be no higher than that.
For horizontal fire spread, the requirement must be divided between the elements. So a 60-minute requirement between two neighbouring buildings can be met by giving both façades 30 minutes of fire resistance.
What does NEN 6069 cover?
Emiel van Rossum: NEN 6069 is used to determine the fire resistance of building elements. The standard refers to European test standards, under which manufacturers have tests carried out in test laboratories, and also sets out the criteria that fire-resistant products must meet.
What are these criteria, and what do they mean?
Emiel van Rossum: For fire separations, the criteria are integrity (E), radiation (W) and temperature (I). The combination required depends on the type of separation. Between two fire compartments, for example, the most stringent criterion, EI, is required. For escape routes, EW is often sufficient because we assume that less combustible material is present there.

What route does a façade contractor usually take to comply with these regulations?
Joep Römgens: The façade contractor will usually pass the requirements they have been given on to the system supplier. They then work together to find the most suitable product. This is often not a straightforward matter of selecting an item from a catalogue, because there are frequently small discrepancies between what is required and what has been tested, such as dimensions, glass type or composition, combinations with side lights and fanlights, and the connection to the main structure.
Do you always receive enough information to offer the right element?
Joep Römgens: Façade contractors often receive incomplete information, for example a WBDBO of 30 or 60, but that is not enough. The EW or EI properties must also be specified in accordance with NEN 6069. Without knowing whether EI or EW is required, a façade contractor does not have enough information to select an element. The direction of fire exposure, from outside to inside or from inside to outside, must also be known.
What is the best thing for a façade contractor to do in that situation?
Joep Römgens: If the picture is incomplete, façade contractors should refer responsibility back to the client, who for the façade contractor is usually the main contractor. The main contractor must in turn obtain the information from their client or their adviser. An important tip for façade contractors: do not interpret or fill in the gaps, insist on receiving complete information.
Who is legally responsible for fire safety?
Emiel van Rossum: The Environment and Planning Act states that this is the building’s owner and/or user. Parties often delegate some of this responsibility by hiring specialists from consultancy firms or construction companies, either during construction or sometimes during the building’s use. However, these parties limit their liability in their terms and conditions. Ultimately, responsibility therefore remains with the owner and/or user.
What advice do you have for façade contractors?
Joep Römgens: If a subcontractor, in this case the façade contractor, offers something that has been incorrectly interpreted on the basis of all the documentation, they can still run into problems, and responsibility may then be passed on to the façade contractor. They therefore need to be fully aware of the requirements. Ask the right questions and get the answers confirmed.